CORROSION COUPON
Environmental Monitoring
Copper-silver corrosion test coupons placed indoors can provide insights into the potential impact of corrosive gases on computer performance after one month. These test coupons are a typical passive monitoring device exposed to the environment, with a monitoring period ranging from 30 to 90 days. The corrosion reports obtained from copper-silver corrosion test coupons represent the cumulative effect of various corrosion layers. This method assesses the “average” environmental conditions over a specific period and is also an indicator of the types and relative severity of corrosive gases.