FFU

Fan Filter Unit (Pharmaceutical)​

FFU

Fan Filter Unit (Pharmaceutical)

Applications

Semiconductor

Pharmaceutical

Healthcare

Cross-Sectional View Of MayAir FFU

ISO 14644 & FS 209E Cleanroom Class

ISO CLASS ISO 14644 FEDERAL STANDARD MAXIMUM PARTICLES PER M3 (PER PARTICLE SIZE SHOWN BELOW)
≥ 0.1 µm ≥ 0.2 µm ≥ 0.3 µm ≥ 0.5 µm ≥ 1.0 µm ≥ 5.0 µm
ISO 1 10
ISO 2 100 24 10 4
ISO 3 Class 1 1000 237 102 35 8
ISO 4 Class 10 10000 2370 1020 352 83
ISO 5 Class 100 100000 23700 10200 3520 832 29
ISO 6 Class 1,000 1000000 237000 102000 35200 8320 293
ISO 7 Class 10,000 352000 83200 2930
ISO 8 Class 100,000 3520000 832000 29300
ISO 9 35200000 8320000 293000

Specifications Table

(AC MOTOR) TECHNICAL DATA

Remark:
1. Test point of noise level is located at 1.5 m (equivalent to 4.9 ft) below the filter downstream.
2. Test point of air velocity is located at 0.15 m (equivalent to 0.49 ft) below the filter.
3. FFU sizes can be customized upon request.
4. FFU power consumption listed are calculated based on FFU intial performance.

(EC MOTOR) TECHNICAL DATA

Remark:
1. Test point of noise level is located at 1.5 m (equivalent to 4.9 ft) below the filter downstream.
2. Test point of air velocity is located at 0.15 m (equivalent to 0.49 ft) below the filter.
3. FFU sizes can be customized upon request.
4. FFU power consumption listed are calculated based on FFU intial performance.

MayAir FFU Control System Configuration Flonet

The MayAir Flonet system is well-suited for efficiently managing a clean room of any size and is able to control both AC and EC types of FFUs.

It offers real-time monitoring and can handle up to 50,000 units within a single system. This system is versatile, allowing control over the entire building’s cleanroom, including separate zones with varying ISO classes. It utilizes a TCP/IP network for signal transmission at speeds of up to 100Mbps, with the option for fiber optic configuration. The system exhibits exceptional stability and response times, with synchronous FFU group scanning taking less than 15 seconds per cycle, and it continues to operate seamlessly even in the event of a lost connection to the server or PC.

MayAir places a strong emphasis on security and has developed a multi-level administration system for control and monitoring. Users receive a unique registration key for software commissioning. User-friendliness is a top priority in the software’s design, featuring a clear navigation tree and a display of theactual cleanroom layout. This ensures users have a more efficient and straightforward experience when monitoring FFUs within the cleanroom.

Downloads

Questions?

Our experts are here for you!